Checking your session…
Sign out

Structural Calculation Set · NSCP-Based

Structural Design Analysis & Calculations

Dead, live, wind, and seismic load computations for a 2–3 storey residential building, with a gravity capacity check — organized as a working calculation sheet set.

Created by Rey Asuncion – Rox-Isa © 2026

Sheet S-0.1

Design Criteria

Governing code, project geometry (set above), and reference values used throughout this workbook.

Governing code
Structural codeNSCP, latest edition
Occupancy categoryResidential (standard)
Importance factor, seismic (I)1.0
Importance factor, wind (Iw)1.0
Standard-occupancy residential construction — not an essential or hazardous facility. Increase importance factors if the structure includes an essential function (e.g. an emergency shelter room).

Typical unit weights (reference)

MaterialUnit weight
Reinforced concrete23.6 kN/m³
Reinforcing steel (density, for bar weight)7850 kg/m³
CHB wall, 100 mm1.53 kPa
CHB wall, 150 mm2.30 kPa
Cement plaster, both faces+0.48 kPa
Floor finish (tile/cement)1.10 kPa
Partition wall allowance0.75 kPa
Suspended ceiling0.24 kPa
GI roofing on purlins0.40 kPa

Typical values commonly referenced from NSCP Table 204-1 material unit weights, plus the standard steel density used in the Bar Bending Schedule's weight calculation. Not exhaustive — live loads (occupancy-based, not material density) are on the Live Loads tab, and soil unit weight is set directly on the Footing tab since it's site-specific. Confirm against the current code edition and actual specified materials before finalizing.

Sheet S-1.1

Dead Load Computation

Superimposed dead load per elevated level. Slab self-weight computed from thickness × concrete unit weight.

Slab & finishes (typical, all levels)

Typical NSCP Table 204-1-based reference values — confirm against the actual finish, ceiling system, and partition layout specified for the project.

Roof level

A concrete roof deck adds its own slab self-weight (thickness × 23.6 kN/m³) on top of the roofing/topping and ceiling allowances above — switch "Roofing + purlins" to the waterproofing/topping option when using a concrete deck.

Sheet S-1.2

Live Load Computation

Minimum uniform live loads by occupancy, typical of NSCP Table 205-1.

Level 2 occupancy
Level 3 occupancy
Roof
Sheet S-2.1

Wind Load Computation

Velocity pressure and design wind pressures — simplified NSCP 207 / ASCE 7-based method.

Wind parameters

This is about your region of the Philippines — how strong typhoons get where the project is (e.g. eastern/northern seaboards facing the Pacific typically see stronger design winds than interior or western-sheltered areas). This is a different question from Exposure category below, which is about the site's immediate surroundings. A coastal lot needs both a higher V here and likely Exposure D below — they're not the same decision, but they often go together. These are typical reference groupings, not a precise province-by-province table; confirm the exact basic wind speed for your specific location against the current NSCP wind speed map.

Exposure is about what's immediately around the site, separate from how strong typhoons get in your region above. As a guide: B — surrounded by buildings, trees, or other obstructions (typical urban/suburban lot); C — open country, scattered obstructions, flat grassland, most provincial lots; D — directly facing open water or a large unobstructed flat expanse with essentially nothing upwind (a beachfront lot facing the sea, a lot at the edge of a large open field). A site right on the coast is exactly the case Exposure D exists for. One nuance worth flagging: in a typhoon-prone country like the Philippines, some coastal sites transition from D back to C a short distance inland from the shoreline rather than keeping D indefinitely — if your site isn't literally on the water's edge, C is often the more defensible choice; verify against the current code's exposure transition provisions if the site is close to this boundary.

Measured from ground surface (grade) up to the roof — for a flat concrete roof (as modeled throughout this tool), that's simply the roof slab's elevation above grade; no slope averaging needed, unlike a pitched roof where "mean" height would average the eave and ridge heights. This field is entered independently — it doesn't auto-calculate from storeys × floor-to-floor height on the Design Criteria tab, since real height can differ slightly (parapet, sloped ground, etc.) — but that product is a reasonable starting estimate: .

Sheet S-2.2

Seismic Load Computation

Static lateral force procedure — base shear per NSCP 208.

Site & system
Sheet S-3.1

Load Summary & Capacity Check

Governing load combinations and a gravity load check on a typical column/footing.

Governing load combinations (NSCP 203, USD)
Combo 11.4D
Combo 21.2D + 1.6L
Combo 31.2D + 1.0W + 1.0L
Combo 41.2D + 1.0E + 1.0L
Combo 50.9D ± 1.0W (or 1.0E)

Listed for reference — the column/footing check below uses Combo 2 (1.2D+1.6L) only, since it's a gravity-only check (tributary area method). Combos 1, 3, 4, and 5 apply to the lateral system (frames or shear walls) and aren't fed into this simplified per-member check — see the Load Combinations section of the Design Report for the full scope note.

Typical column / footing check

Tributary area = (adjacent bays) × (Lx/2) × (Ly/2) — a corner column touches 1 bay, an edge column 2, and an interior column 4. Uses the diagram convention where 45° lines split each bay's load to its nearest column.

Presumptive bearing values are typical figures used for preliminary sizing only — they are not a substitute for an actual geotechnical/soil investigation, which governs the final design value. The NSCP Table 304-1 group reflects the code's own presumptive bearing table (for cases where no site investigation has been performed, per NSCP Section 304.2 — an increase of up to 20% per additional 300mm of footing width/depth beyond the minimum 300×300mm applies per the code, not modeled here). These figures were sourced from an available reference copy of the table, not independently verified against your specific NSCP edition — confirm the exact classification names and values against your own current copy before relying on them.

Sheet S-3.2

Member Design Checks

This is where individual members get sized and checked — enter trial dimensions and reinforcement, and each check compares factored demand (U) against design capacity (φRn) to return Pass or Fail. Simplified singly-reinforced / axial-only checks — no deflection, development length, or ductile-detailing verification.

Member identification

Saves just this beam's inputs — not the whole project — so you can build up a set of named checks (e.g. corner-B1, edge-B2, interior-B3) without one overwriting another. Suggested filename uses the position and mark set above.

Section & materials

f'c is set by the concrete mix class ordered from the plant; fy is set by the rebar grade per PNS 49. Pick a standard value above or type your project's exact spec directly.

Reinforcement (tension, bottom)

With auto-calculate on, the bar count is set to the minimum needed to satisfy Mu for whichever bar size you pick above — change the size and the count recalculates. Uncheck to type your own count instead; PASS/FAIL is still checked either way.

Top reinforcement (hanger / compression bars)

Auto-calculates from the negative-moment demand when the span is continuous, or the primary tension demand when it's a cantilever — otherwise (simply supported) there's no moment for top bars to resist, so it defaults to the standard 2-bar minimum needed to hold the stirrup corners closed. Uncheck to type your own count.

Side (skin) reinforcement

Only needed on deep beams — checked automatically from d below.

Stirrups

Ductile detailing calls for closer stirrup spacing near each support face than at midspan — that zone sees higher shear and needs better confinement, especially relevant given most of the Philippines is Seismic Zone 4. Confinement zone length is taken as 2h (2× overall beam depth) from the face of each support, a standard reference length — confirm the exact zone length and spacing limits against the current NSCP/ACI 318 seismic detailing provisions (Chapter 4 special moment frame requirements) for anything beyond preliminary sizing.

Loading — pulled from Dead/Live sheets

Sets the span condition above to match. Interior, Edge, and Corner all currently use the same "Continuous" representative coefficient (wL²/10) — this tool's moment coefficients don't yet distinguish an end span from a fully interior one, the same simplification already flagged elsewhere. Pick "Isolated span" for a genuinely simply-supported beam, or change the Span condition above directly for a cantilever.

Point load (optional — e.g. a stair reaction landing on this beam)

A point load is added on top of the tributary UDL above using superposition (Mu = Mu,udl + P·a·(L−a)/L for supported spans, or P·a at the fixed end for a cantilever, with a measured from that support). Exact for simply-supported/cantilever; a reasonable, typically conservative approximation for "continuous."

Stair flight load calculator (optional helper)
Member identification

Saves just this slab's inputs — build up a set of named checks (corner/edge/interior panels) without one overwriting another.

Section & materials

f'c is set by the concrete mix class ordered from the plant; fy is set by the rebar grade per PNS 49 (Philippine National Standard for Steel Bars). Pick a standard value above or type your project's exact spec into the field directly.

Short-direction reinforcement (per metre width)

With auto-calculate on, spacing is set to the tightest 10mm-increment value needed to satisfy the moment demand for whichever bar size you pick — change the size and the spacing recalculates. Uncheck to type your own spacing instead; PASS/FAIL is still checked either way.

Loading — pulled from Dead/Live sheets
Panel dimensions

Panel aspect ratio (W/L) determines whether this is a one-way or two-way slab — see the flag in the results.

Member identification

Saves just this column's inputs — build up a set of named checks (corner/edge/interior columns) without one overwriting another.

Section & materials

f'c is set by the concrete mix class ordered from the plant; fy is set by the rebar grade per PNS 49. Pick a standard value above or type your project's exact spec directly.

Longitudinal reinforcement (tied column)

With auto-calculate on, bar count is set to the minimum needed to satisfy Pu (and the 1% minimum steel ratio) for whichever bar size you pick — change the size and the count recalculates. Uncheck to type your own count instead; PASS/FAIL is still checked either way.

Ties

Closer tie spacing is required near each beam-column joint (top and bottom of the column) than at mid-height — that zone sees the highest demand during a seismic event, especially relevant given most of the Philippines is Seismic Zone 4. Confirm the exact joint zone length and spacing limits against the current NSCP/ACI 318 special moment frame provisions for anything beyond preliminary sizing.

Demand
Member identification

This footing's load already reflects its column's tributary position (corner/edge/interior), set on the Summary sheet — shown here for reference, not editable directly.

Resets this footing's own fields — including its size — thickness, depth, materials, bars, embedment. Since footing size also feeds the bearing check on the Summary sheet, that display updates too once cleared.

Saves just this footing's inputs — build up a set of named checks (corner/edge/interior footings) without one overwriting another.

Footing & column geometry

To change the footing size, use "Proposed square footing side" on the Summary & Check sheet — that's the actual value every calculation here uses. This field is a read-only mirror, shown for reference so you don't have to switch tabs to see it.

Bottom reinforcement (per metre width)

With auto-calculate on, spacing is set to the tightest 10mm-increment value needed to satisfy the flexural demand at the column face for whichever bar size you pick. Uncheck to type your own spacing instead; PASS/FAIL is still checked either way.

f'c is set by the concrete mix class ordered from the plant; fy is set by the rebar grade per PNS 49. Pick a standard value above or type your project's exact spec directly.

Top reinforcement (temperature/shrinkage)

Under this tool's axial-only column model (no P-M interaction, flagged elsewhere), a footing genuinely only develops bottom-face tension — there's no calculated top-bending demand here, so these are minimum temperature/shrinkage bars, not a flexural design. If the actual column transmits significant moment to the footing, or the footing could see net uplift, that's a real top-face tension case this tool doesn't check — get that reviewed separately by the Engineer of Record.

Embedment depth (Rankine's minimum depth of foundation)

Weaker soils conventionally need a deeper minimum embedment — to get below an unreliable surface layer and ensure adequate confinement — while rock can often bear adequately much closer to the surface. These are typical reference values, not a fixed code minimum; the actual required depth should come from your geotechnical report.

Demand Pu and footing size B are read from the Summary & Check sheet (tributary column load and proposed footing) — adjust the inputs there to change the loads used here.

Member identification
CHB wall carried

A continuous strip footing running beneath a non-structural CHB partition or perimeter wall, tying its base together and providing a bearing surface wider than the wall itself — separate from the column footings, which carry the building's actual structural loads. This footing mainly carries the wall's own light self-weight.

Footing geometry
Reinforcement
Blinding concrete (seating below the footing)

A thin plain (unreinforced) lean-mix concrete layer poured on prepared/leveled ground before the wall footing above it is built. Typically 50–75mm thick, lean mix, no reinforcement — a placement provision, not a strength calculation.

Sheet S-3.5

Stair Design

Designs the stair's own waist slab (an inclined one-way slab) — separate from the "Stair reaction" helper on the Beam tab, which only computes the point load a stair applies to a supporting beam. This checks the stair itself.

Member identification
Stair type & geometry

Riser is a target — the tool solves for the number of risers that divides the total rise evenly, then reports the actual riser this gives you (usually within a few mm of the target). Comfort/code guidance: individual riser 150–200mm, tread 250–300mm, and 2R+T generally in the 600–650mm range — checked below.

Waist slab
Loads

4.8 kPa is the typical NSCP live load for stairs — heavier than a normal residential floor, since stairs see concentrated, dynamic pedestrian traffic.

Main reinforcement (along the incline, per metre width)
Distribution reinforcement (across the width, per metre length)

Minimum temperature/shrinkage steel (0.0018 × gross area), same basis as the footing's top reinforcement — this is a code minimum, not a calculated flexural requirement, since distribution steel doesn't carry the main span moment.

Sheet S-3.3

General Notes & Specifications

Standard structural general notes, an auto-compiled materials specification summary, and space for project-specific notes.

General notes
  1. All construction shall conform to the National Structural Code of the Philippines (NSCP), latest edition, and the National Building Code of the Philippines (PD 1096) and its Implementing Rules and Regulations.
  2. Design loads, load combinations, and wind/seismic parameters are as indicated on Sheets S-0.1 through S-3.1 of this set.
  3. Concrete: normal-weight, unit weight 23.6 kN/m³ unless noted; f'c per member as scheduled in the Materials Specification Summary below.
  4. Reinforcing steel: fy per member as scheduled below, conforming to PNS 49 (Philippine National Standard for Steel Bars).
  5. Minimum concrete cover, unless noted otherwise: 75 mm for footings cast against earth; 40 mm for beams, columns, and footings not cast against earth; 20 mm for slabs.
  6. Lap splices for reinforcing bars shall be Class B tension splices unless noted otherwise; splice locations shall avoid regions of maximum stress where practicable.
  7. All dimensions are in millimeters and elevations in meters unless noted otherwise.
  8. The Contractor shall verify all dimensions, levels, and site conditions before commencing work and shall notify the Engineer of any discrepancy.
  9. Shop drawings for reinforcement (and structural steel, if any) shall be submitted for the Engineer's review prior to fabrication.
  10. This workbook is a preliminary design-computation reference. It shall not be used for construction until reviewed, signed, and sealed by the Engineer of Record.
Materials specification summary (auto-compiled)
Project-specific notes

Project-specific notes are included when you Save the project file, so they carry over the next time you Load it.

Sheet S-3.4

Structural Specifications

Material, workmanship, and quality-control provisions — the technical specification companion to the General Notes and computations above.

1. Concrete
  1. Ready-mixed concrete shall conform to ASTM C94 (or equivalent PNS standard). Cement shall be Portland cement, ASTM C150 Type I, unless a different type is noted for sulfate exposure or other site conditions.
  2. Aggregates shall conform to ASTM C33. Water shall be clean and potable, free of oil, acid, or organic matter.
  3. Concrete strength class (f'c) for each member is as scheduled on the Materials Specification Summary (General Notes sheet) and the Member Design sheet. Maximum water-cement ratio and slump shall follow the approved mix design for the specified class — typical slump range 75–100 mm for conventionally placed structural concrete, adjusted for pumping or congested reinforcement as needed.
  4. Formwork shall remain in place until concrete reaches sufficient strength to support its own weight and construction loads — typical minimum stripping times: vertical forms (columns, walls) 24 hours; beam and slab soffits, shored until concrete reaches 70% of specified f'c or per the Engineer's written approval.
  5. Concrete shall be moist-cured for a minimum of 7 days (or per ACI 308 for the specific cement type and ambient conditions) following placement.
  6. Testing: sample and test concrete per ASTM C172 (sampling), C31 (cylinder preparation), and C39 (compressive strength). Typical minimum frequency: one set of test cylinders per 40 m³ of concrete placed, or per day's pour, whichever gives more sets, with at least one set per structural element type per pour.
2. Reinforcing steel
  1. Deformed reinforcing bars shall conform to PNS 49, of the grade scheduled on the Materials Specification Summary and Member Design sheet for each member.
  2. Bar bending and fabrication shall conform to the approved shop drawings; field bending of bars partially embedded in concrete is not permitted without the Engineer's approval.
  3. Minimum concrete cover and lap splice requirements are as stated in the General Notes sheet. Mechanical couplers, if used in place of lap splices, shall develop at least 125% of the bar's specified yield strength.
  4. Mill test certificates shall be furnished for each heat/batch of reinforcing steel delivered to the site, confirming grade and chemical/mechanical properties.
3. Earthwork & foundation
  1. Excavate to the bearing stratum assumed in the design or identified in the geotechnical report, at minimum to the governing embedment depth computed on the Footing sheet. Notify the Engineer if the bearing stratum encountered differs from what was assumed.
  2. The foundation subgrade shall be free of loose soil, debris, and standing water immediately prior to placing lean concrete or footing concrete.
  3. Backfill around foundations shall be placed in lifts and compacted to at least 90–95% of maximum dry density (standard or modified Proctor, per the geotechnical report), avoiding damage to waterproofing or foundation walls.
4. Quality control & inspection
  1. Special inspection shall be performed where required by NSCP and the local Office of the Building Official, including but not limited to concrete placement, reinforcing steel placement prior to concrete pour, and soil bearing verification at footing excavations.
  2. An accredited testing laboratory shall perform concrete cylinder testing, and shall furnish written reports to the Engineer and the Contractor.
  3. Shop drawings, concrete mix designs, and material certificates shall be submitted to the Engineer for review before fabrication or placement begins.
  4. Any deviation from the approved structural drawings and this specification requires the Engineer's written approval before work proceeds.
Project-specific specifications

Standard clauses above reflect common ASTM/ACI/PNS practice — confirm exact requirements, testing frequencies, and standards references against the current codes and the project's actual geotechnical report before issuing for construction. Project-specific specifications are included in Save/Load, same as the General Notes.

Sheet S-4.1

Structural Design Analysis and Computations

Draft prepared for review, correction, and sealing by the licensed Engineer of Record — compiled from every sheet above into the document form typically bound with the structural drawings for permit submission.

Report header
Engineer of record
This tab compiles the entries and results from every other sheet into one document. Fill in the header fields, switch to this tab, then use Print / Save as PDF — the tab strip and input forms are hidden automatically in the printed output. The status line updates to match "Review status" above — but it can never be turned off entirely, and none of its states claim the document is sealed. Only the Engineer of Record's actual signature and PRC seal in the box below does that; the status line just tracks where the draft stands on the way there.
Sheet S-4.2

Building Permit Submission Checklist

Documents commonly required alongside the structural report for a building permit application in the Philippines (National Building Code, PD 1096 and its IRR). Requirements vary by city/municipality — confirm the exact list with your Office of the Building Official (OBO) before filing.

Application & site documents
  • Duly accomplished Building Permit Application form
  • Proof of property ownership (TCT) or authority to build (e.g. contract of lease, owner's consent)
  • Current Tax Declaration and latest real property tax receipt
  • Lot plan / vicinity map prepared by a Geodetic Engineer
  • Barangay clearance and/or HOA clearance, where applicable
Structural documents (this report supports these)
  • Structural design plans — foundation, framing, and detail sheets
  • Structural design analysis / computations, signed and sealed by a Civil Engineer
  • Soil investigation / geotechnical report, where required by the OBO or building size
  • Bill of materials and cost estimate, signed and sealed
  • Specifications
Other engineering plan sets
  • Architectural documents, signed and sealed by an Architect
  • Sanitary / plumbing plans, signed and sealed by a Sanitary Engineer or Master Plumber
  • Electrical plans, signed and sealed by a Professional Electrical Engineer
  • Mechanical plans, where applicable (elevators, HVAC)
  • Electronics/fire alarm plans, where applicable
Clearances
  • Fire Safety Evaluation Clearance, Bureau of Fire Protection
  • DENR/ECC certificate, for projects that require it
  • Contractor's PCAB license and business permit, at construction stage

This list covers the documents typically requested; some LGUs add locality-specific requirements (e.g. traffic management plan, DPWH road right-of-way clearance for frontage on a national road). Always verify the current checklist with the OBO where the project will be filed.

Sheet S-4.3

Bar Bending Schedule

Cutting lengths and quantities for every bar already entered on the Member Design sheet — auto-compiled, not re-entered. Straight bars use the member's own dimension as the base length; stirrups/ties add standard hook allowances to the closed-loop perimeter.

Concrete cover

Used only for the stirrup/tie closed-loop perimeter calculation below (perimeter is measured to the outside of the bar, inside the cover). 40mm and 75mm are common typical values, not universal minimums — confirm the actual cover called for by your project's exposure condition and the current NSCP cover table.

Stirrup/tie hook

Hook extension used: max(6×bar dia, 75mm) per end for 135°, max(12×bar dia, 75mm) for 90° — a commonly-cited simplified rule (90° hooks anchor less effectively per unit length than 135°, so conventionally need a longer tail). Exact minimum extensions can vary slightly by hook angle and bar size break-point in the current code table (NSCP/ACI 318 Ch. 25) — confirm before final detailing, especially for anything larger than typical 10–12mm ties.

Beam bar anchorage into column

When enabled, adds a standard 90° hook (extension = 12×bar dia, per ACI 318/NSCP Table 25.3.1 for standard bar hooks — a different, larger provision than the stirrup/tie hook above) at both ends of the beam's bottom and top bars, so they properly anchor into the column at each support rather than just running straight to the column face. Turn this off for a bar that continues straight through as part of a longer continuous run instead of terminating at a column.

Column vertical bar lap splice

Adds one splice length to the column vertical bar's total, representing the lap where this floor's bars splice into the next floor up. 40×bar dia is a commonly-cited simplified/typical value for column bar splices — it is not the full ACI 318 development-length calculation (which depends on concrete strength, bar coating, spacing, and several other factors) — confirm the actual required splice length once those are finalized. Set to 0 for a single-storey column with no splice needed.

Stock bar procurement

Used to estimate how many full-length stock bars to actually order per diameter — cut pieces shorter than one stock length are packed together (offcuts from one bar mark can serve a shorter cut from a different one, same diameter) to minimize waste; pieces longer than one stock length need splicing across multiple bars. 6m is the most common commercial length in the Philippines — change this to match what your supplier actually stocks.

Sheet S-5.1

Fence Design

Independent from the main house — a fence is wind-governed, not gravity-governed: the post is a cantilever fixed at the ground, resisting lateral wind pressure on the fence face rather than floor loads.

Fence geometry & wind pressure

Reuses velocity pressure qz from the Wind Loads sheet (same basic wind speed, exposure, and height entered there). A longer, more continuous fence run generally has a lower Cf than a short, isolated wall section — these are typical reference groupings, not a precise aspect-ratio table; verify against your actual fence run length for anything unusual.

Fence layout

Total fence length above should be the full run including where the gate(s) sit — this opening width is subtracted from it before estimating line posts, and each gate adds its own two gate posts (hinge + latch) to the count below, matching the "Gate post" option on the Post Design tab.

Member identification

The Fence Layout tab estimates total posts split by type (corner/line/gate) — match this count to whichever post type is selected below, since they can have different sizes or reinforcement.

Section & materials
Reinforcement (both faces — wind reverses)
Ties
Loading
Soil resistance (simplified uniform passive pressure)
Member identification
Wall & materials

These two presets are a practical/economic distinction, not a code-mandated split — there's no NSCP provision that specifically differentiates "house" from "farm" fence material grades. A farm/perimeter fence is typically simpler, lower-cost construction (leaner grout mix, lighter rebar grade, often longer runs with lower architectural finish), while a house fence tends toward a somewhat richer mix and heavier bar grade for a more finished result. Confirm against your actual project's masonry specification either way. CHB (concrete hollow block) walls are treated here as reinforced masonry — vertical bars grouted into filled cells, checked with the same flexure approach as reinforced concrete but using the grout/fill strength as f'c. d defaults to roughly half the block thickness, since CHB reinforcement typically sits centered in the cell. This is a simplification, not a full masonry design per NSCP Chapter 7 — adequate for preliminary sizing, not a substitute for masonry-specific code checks on a real project.

Reinforcement (vertical bars in filled cells)

These vertical bars are what the flexural span check above uses, in whichever direction (horizontal or vertical) is actually selected as the span condition — a common simplification for preliminary CHB sizing. The horizontal bond beam bars below are a separate, additional component every real CHB wall needs regardless of which direction governs flexure — for shrinkage/temperature control and out-of-plane stability, not modeled as part of the span check itself.

Horizontal reinforcement (bond beam, post to post)

Bond beam courses running the full length between posts (post spacing), typically every 600–800mm up the wall height (roughly every 4th CHB course at standard 200mm block height) — a common detailing practice, not a single hard NSCP figure. Adjust to match your actual block coursing.

Wall footing (strip footing below the CHB wall)

A continuous strip footing running the full wall length, tying the CHB wall base together and providing a bearing surface wider than the wall itself — separate from the individual post footings, which carry the actual lateral wind load through their own embedment. This footing mainly carries the wall's own light self-weight, not wind. The reinforcement below is designed per post-to-post bay — set the count above to however many bays share this same design.

Wall footing reinforcement
Blinding concrete (seating below the wall footing)

A thin plain (unreinforced) lean-mix concrete layer poured on prepared/leveled ground before the wall footing above it is built — provides a clean, level, stable seating surface and keeps the actual structural concrete from direct contact with variable soil. Sits directly below the footing, wider than the footing itself on each side. Typically 50–75mm thick, lean mix (e.g. 1:3:6 class), no reinforcement, no structural design check — this is a placement/workmanship provision, not a strength calculation, so only its material quantity is computed here.

Span condition

"Horizontal" uses the post spacing from the Post Design tab as its span. "Vertical cantilever" uses the full fence height with no restraint at top. "With tie beam" also uses the fence height as the span, but as a simply-supported (not cantilevered) panel — appropriate once a tie beam is added partway up (see the Tie Beam tab), which restrains the top of this lower wall segment and roughly quarters the moment compared to a full cantilever of the same height.

Member identification

Use this when the fence is tall enough that a single CHB run from footing to top can't reasonably pass the CHB Wall Panel check as a full-height cantilever — an intermediate horizontal tie beam splits the wall into a shorter lower panel (now simply supported, not cantilevered — select that option on the Wall Panel tab) and a shorter upper panel above the beam.

Section & materials

Same standard classes used throughout this workbook — pick one or type your project's exact spec directly.

Reinforcement (both faces — wind reverses, same reasoning as the post)

This beam bends sideways under wind, not downward under gravity — the load pushes perpendicular to the wall face, so tension can land on either side depending on which way the wind is blowing that day. Same logic as the fence post's symmetric reinforcement: equal bars on both faces, not just one "bottom" face.

Ties/stirrups
Location
Loading

Tributary height is always exactly half the total fence height, regardless of where along the height the beam sits — with uniform wind pressure, the beam always picks up half the load from the segment above it and half from the segment below, and those two halves always sum to H/2. Auto-computed from Wind Pressure tab's fence height. Span defaults to the post spacing — the beam runs horizontally between posts, same as the wall panel it's supporting.

Bar Bending Schedule settings

Same method and conventions as the house's Bar Bending Schedule sheet, independent settings.

Stock bar procurement
Fence general notes
  1. All fence structural work shall conform to the National Structural Code of the Philippines (NSCP), latest edition, and the National Building Code of the Philippines and its IRR.
  2. Fence posts shall be embedded to at least the depth shown on the Embedment Depth sheet, backfilled with concrete or well-compacted select fill as specified — not loose backfill.
  3. Fence posts do not require a separate spread footing or blinding layer beneath them — the post resists lateral wind load through soil confinement along its embedded depth (passive pressure), not through vertical bearing on a widened base, so the embedment depth itself is the complete foundation design for the post. This is different physics from a column-on-footing system, and different from the Wall Footing between posts (below), which does carry a genuine vertical bearing load from the CHB wall's self-weight and does need blinding beneath it.
  4. CHB (concrete hollow block) fence walls shall have all cells containing vertical reinforcement filled solid with grout for the full height of the wall.
  5. Corner, end, and gate posts typically require greater embedment depth, larger sections, or additional bracing than a typical line (intermediate) post, due to unbalanced or concentrated loading — this is not evaluated here, which checks a typical line post only.
  6. A weep hole or drainage provision at the base of solid CHB fence walls is recommended to relieve water pressure buildup behind the wall.
  7. Expansion/control joints in long CHB fence runs shall be provided at intervals per standard masonry practice (typically every 6–9 m, or as detailed) to control shrinkage cracking.
  8. Where an intermediate tie beam is used, it shall be reinforced symmetrically on both faces (not just the bottom) — wind can push from either direction, so tension can develop on either face depending on wind direction that day.
  9. This sheet is a preliminary design-computation reference. It shall not be used for construction until reviewed, signed, and sealed by the Engineer of Record.
Fence specifications
  1. Fence post holes shall be excavated to the dimensions and depth shown on the Embedment Depth sheet, with the bottom of the hole free of loose material immediately before setting the post. No blinding course or formed footing pad is required beneath the post itself — this applies only to the Wall Footing between posts, where blinding is specified separately on that sheet.
  2. Where posts are set in concrete, the concrete shall be a minimum of the class specified for the post itself and shall be consolidated to eliminate voids around the embedded post.
  3. CHB units shall conform to PNS standards for concrete hollow blocks; grout for filled cells shall achieve the compressive strength scheduled on the CHB Wall Panel sheet.
  4. Vertical reinforcing dowels shall extend from the footing/post into the CHB wall cells for the full required splice length, and shall be secured in position before grouting.
  5. Fence alignment, plumbness, and top-of-wall/post elevations shall be verified by survey before and after concrete/grout placement.
  6. Where an intermediate tie beam is called for, it shall be cast monolithically with the CHB wall's grouted cells at that course, and its reinforcement shall be continuous through (or properly spliced at) each post it passes, not simply butted against the post face.
Fence-specific notes (project)

Included in Save/Load, same as the house's project notes.

Report header
Engineer of record
This is a fully independent report from the house's Design Report — its own header, its own Engineer of Record block, its own status, its own print output. Fill in the fields, then Print / Save as PDF.
Project2–3 Storey Residential Building
Sheet SetStructural — Preliminary Loads
CodeNSCP, latest ed.
StatusFor SE review & sealing